110 CF3000 INSTALLATION AND OPERATION MANUAL 25-14682-A July 2019 www.eaton.com
Appendix
Detector base wiring (CAB300)
Supply voltage
18 - 30 V DC
Cable size
1.0 - 1.5mm²
Recommended cable types
FIRETUF, FP200 or MICC
Mounting hole centres
50 - 80mm
Wiring hints
Each terminal is suitable for clamping up to 2 wires
Clamping of 2 wires of very different diameters under one screw
is not recommended
Suitable for mounting to mounting boxes with 50-80mm fixing centres
General
If difficulty is experienced when mounting the sensor, this may be due
to the following:
Wiring causing an obstruction - move or shorten wires
Although the base is tolerant to uneven mounting surfaces, a very uneven surface
may cause the base to deform when the mounting screws are tightened down -
loosen screws to reduce this or slide base to a flat position
WARNING
DO NOT USE HIGH VOLTAGE TESTERS WHEN
SENSORS OR CONTROL PANEL ARE CONNECTED TO
THE SYSTEM.
++
SS ++
FF
FF ++
SS
__
__
__
__
__
__
__
__
__
__
RReemmoottee
IInnddiiccaattoorr
LLEE DD
((ooppttiioonnaall))
++VV IINN
-- VV EE CC OO MM OO UU TT
Compatible
AAnnaalloogguuee AAddddrreessssaabbllee
FF iirree AAllaarrmm PP aanneell
EE aarrtthh ss ccrree eenn ooff ccaabbllee ttoo bb ee cc oo nnttiinnuuoouuss bbeettwweeee nn ss ee nnss oorrss
LLoooopp SSttaarrtt
LLoooopp FFiinniisshh
-- VV EE CC OO MM IINN

Table of Contents

Related product manuals