40 CF3000 INSTALLATION AND OPERATION MANUAL 25-14682-A July 2019 www.eaton.com
Technical specification
Optional functions as per EN54 P2&4
The panel is approved to EN54 Parts 2 & 4 including all the following options which
can be selected as required
Panel outputs
Panel Sounders: (OPTION 7.8 EN54 PT 2)
Two pairs of outputs are provided. ONLY polarised equipment should be used.
Ensure the polarity of the connections are observed at all times and end of line
resistors (6K8 5%) are fitted for correct operation.
The total alarm load across all sounder outputs = 1.5 Amp
All outputs are fused with 1.6 Amp Glass fuse Alarm devices should be spread
equally across the 4 sounder circuits.
WARNING
Do not exceed the rated output current
Output fire alarm routing equipment
(Option 7.9 EN54 PT 2)
This output, which is fused, and monitored using a 6.8k end of line resistor, is used
for the automatic transmission of the fire signals to fire alarm routing equipment
(e.g. Fire brigade). It operates by providing 24 Volt output to an auxiliary device ( e.g.
relay).
It is current limited to 30 mA using a resettable polyswitch. Class change and test
conditions do not operate this output. If operated under a fire alarm condition, the
indication will be displayed on the Touch screen display and will remain until the fire
alarm is reset.
Ensure the polarity of the connections are observed at all times and end of line
resistors ( 6K8 5% ) are fitted for correct operation.
Output to fire alarm protecting equipment
(Option 7.10 EN54 PT 2)
This output, which is fused, and monitored using a 6.8k end of line resisters used
for the transmission of the fire signals to controls for automatic fire protecting
equipment (e.g. Door released units etc).It operates by providing 24 Volt output to an
auxiliary device ( e.g. relay).
It is current limited to 30 mA using a resettable. polyswitch. Class change and test
conditions do not operate this output. If operated under a fire alarm condition , this
output remains energised until the fire alarm is reset.
Ensure the polarity of the connections is observed at all times and end of line
resistors ( 6K8 5% ) are fitted for correct operation.