EasyManua.ls Logo

Eaton CF3000 - Base Sounder VAD (CASBB394)

Eaton CF3000
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
114 CF3000 INSTALLATION AND OPERATION MANUAL 25-14682-A July 2019 www.eaton.com
Appendix
Base Sounder VAD (CASBB394)
Installation
1. Installation is simple using first fix base.
2. First fix base is fixed to mounting surface via 2 fixings holes.
3. Cables enter through aperture in base (rear entry only).
4. Main body is then clipped into place on base, main body locks into place when
pressed into position.
5. Cables pass through aperture in sounder body and terminate at the front.
6. Connections are to connector block on front of main sounder body.
System functionality
1. Volume and tone are set by control panel, no need to access
sounder to alter setting.
2. Soft addressed.
Standard connections
ote:N Base terminal 1, 2, 3 and 4 not used. All wiring terminates as shown above.
WARNING
Do NOT use high voltage testers if ANY equipment
is connected to the system. Earth screen must be
continuous along entire length of loop.
2
4
1
3
E
LED
+ - + -
2
4
1
3
E
LED
+ - + -
Compatible
Intelligent Addressable
Control Panel
Loop finish
Loop start
S+
S-
F+
F-

Table of Contents