3
1 Introduction / Foreword
Installation and Operating Instructions CGLine+ Web-Controller 40071860236 (E) February 2019 www.eaton.com
1 Introduction / Foreword
The CGLine+ Web-Controller allows for comfortable and full
control and monitoring for up to max. 800 CGLine+ self-
contained luminaires or modules. Many useful features are
implemented.
The luminaires are connected via a 2 core bipolar buscable,
subdivided on 4 or 2 lines (max. 200 luminaires on 4 lines or
400 luminaires on 2 lines).
An integrated webserver allows an easy monitoring of all
luminaires over an existing computer network, via a stan-
dard web browser, e.g. firefox. Thus a special software is not
required and location independent monitoring is possible.
An optional CGLine+ PC-Software allows an comfotable con-
figuration of the CGLine+ Web-Controller via an USB-cable
connection.
The following features are available:
n
Housing for DIN rail mounting in a standard distribution
cabinet
n
Up to 4 lines with max. 200 luminaires each, in total max.
800 luminaires
n
Íntegrated webserver for a comfortable monitoring via
standard webbrowser
n
Integrated mail client for up to 10 recipients, mail events
freely selectable
n
Blocking input with differential loop monitoring
(1 kOhm)
CGLine+ Web-Controller: With inte-
grated memory for storing the con-
Visualisation of up to 800 luminaires
(4 lines with max. 200 luminaires each or
2 lines with max. 400 luminaires each, only
with homogeneous installation of CGLine+
luminaires)
CGVision software: Configuration
and full visualisation of 32 x 800
Network PC or CGLine+ Wireless
Monitoring Set (optional): Access to
USB stick: For convenient logbook
analysis at the PC
Up to 32 controllers with 800
luminaires each (only with
homogeneous installation of
CGLine+ luminaires)
...
Ability to store the configu-
ration and logbook via USB
stick
Line 1
Line 2
Line 3
Line 4
n
Two free programmable digital inputs
n
Two free programmable relay outputs (changeover con-
tacts)
n
Automatic luminaire search function (no manual address-
ing required)
n
Automatic function / duration test of all luminaires,
assigned into 8 test groups
n
Luminaires with maintained light can be switched off, free
selectable (in non-maintained light)
n
2 x USB ports,1 x for Backup via USB-stick, 1 x for easy con-
figuration via CGLine+ PC-software
n
Intergrated building layout programming with max. 30 lay-
outs (external software as option)
n
Downloadable logbooks
n
CGVision fully configuration and monitoring software for
max. 32 CGLine+ Web-Controller available (as option)
IMPORTANT
The CGLine+ Web-Controller is compatible with the older
CGLine self-contained system. If one or more CGLine luminaire
is connected, the controller switches automtically to CGLine
compatibility modus. Some CGLine+ features are not available
then.
NOTE
For setting up the Adaptive Evacuation mode, please read the
AE manual.
Fig. 1. Application example