SPECIFICATIONS
EATON Powerware
®
9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com
54
Table 5. Electrical Input
120V Models 230V Models
Nominal Voltage 120V default; 110, 120, 127V selectable* 230V default; 220, 230, 240V selectable*
Voltage Range 80–144V for 110, 120, 127V nominal 160–288V for 220, 230, 240V nominal
Nominal Frequency 45–65 Hz, 50/60 Hz auto-sensing
Noise Filtering MOVs and line filter for normal and common mode noise
Connections 700–1500 VA: 6-ft, 5-15P power cord
2000 VA: 6-ft, 5-20P power cord
10A, IEC 320-C14 input connector
* 208V nominal input voltage is available. Contact the Help Desk at one of the telephone numbers on page 60 for
assistance.
Table 6. Electrical Output
120V Models 230V Models
Power Levels (Rated at
Nominal Inputs)
PW9125 700: 700 VA, 490W
PW9125 1000: 1000 VA, 700W
PW9125 1250: 1250 VA, 875W
PW9125 1500: 1500 VA, 1050W
PW9125 2000: 2000 VA, 1400W
PW9125 2000 20R: 2000 VA, 1400W
PW9125 700i: 700 VA, 490W
PW9125 1000i: 1000 VA, 700W
PW9125 1250i: 1250 VA, 875W
PW9125 1500i: 1500 VA, 1050W
PW9125 2000i: 2000 VA, 1400W
Regulation
(Normal Mode)
Nominal output voltage ±3%
Regulation
(Battery Mode)
Nominal output voltage ±3%
Voltage Waveform Normal mode: Sine wave; <5% THD with full PFC and nonlinear load
Output Receptacles (6) 5-15R
PW9125 2000 20R only: (4) 5-20R, (2) 5-15R
(6) IEC-320