SPECIFICATIONS
EATON Powerware
®
9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com
55
Table 7. Environmental and Safety
120V Models 230V Models
Operating Temperature 0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Relative Humidity 5–90% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Transit Altitude Up to 10,000 meters above sea level
Heat Dissipation
(Recharge Mode up to
8 Hours)
700 VA: 472 BTU/hr
1000 VA: 601 BTU/hr
1250 VA: 879 BTU/hr
1500 VA: 986 BTU/hr
2000 VA: 1201 BTU/hr
Audible Noise Less than 45 dBA Normal mode, typical load
Less than 50 dBA Battery mode
Surge Suppression ANSI C62.41 Category B (formerly IEEE 587)
Safety Conformance UL 1778, UL 497A;
CSA C22.2, No. 107.1, 107.2;
NOM-019-SCFI
UL 1778, UL 497A;
CSA C22.2, No. 107.1, 107.2;
EN 62040-1-1 and IEC 60950-1;
NOM-019-SCFI
Agency Markings cULus, CSA, NOM cULus, CSA, CE, NOM, NEMKO
EMC (Class B) FCC Part 15, ICES-003, VCCI EN 50091-2, FCC Part 15, ICES-003, VCCI
Table 8. Battery
UPS Configuration 700–1000 VA: (2) 12V, 9 Ah internal batteries
1250–2000 VA: (4) 12V, 9 Ah internal batteries
EBM Configuration PW9125 24 EBM: (8) 12V, 9 Ah
PW9125 48 EBM: (8) 12V, 9 Ah
Type Sealed, maintenance-free, valve-regulated, lead-acid
Charging Internal battery: approximately 2 hours to 80% usable capacity
at nominal line voltage after full load discharge
External battery: no more than 10x discharge time to 90% usable capacity
at nominal line voltage after full load discharge
Monitoring Advanced monitoring for earlier failure detection and warning