SPECIFICATIONS
EATON Powerware
®
9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com
56
Table 9. Battery Runtimes (in Minutes)
700–1000 VA Models
Load
UPS Internal
Batteries
+1 EBM +2 EBMs +3 EBMs +4 EBMs
200 VA/140W 37 271 546
400 VA/280W 19 142 278
700 VA/490W 9 72 156
850 VA/595W* 6 59 124
1000 VA/700W* 5 48 104
* Runtimes do not apply for 700 VA models.
1250–2000 VA Models
Load
UPS Internal
Batteries
+1 EBM +2 EBMs +3 EBMs +4 EBMs
400 VA/280W 46 177 331 501 682
700 VA/490W 25 96 180 272 370
850 VA/595W 21 76 142 214 292
1000 VA/700W 16 61 115 174 237
1250 VA/875W 11 46 87 131 179
1500 VA/1050W** 8 37 70 106 144
1800 VA/1260W*** 6 30 57 85 116
2000 VA/1400W*** 5 26 49 74 100
** Runtimes do not apply for 1250 VA models.
*** Runtimes do not apply for 1250 VA and 1500 VA models.
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.