9355 UPS (20/30 kVA) Installation and Operation Manual S 164201626 Rev B www.powerware.com
9
Chapter 3 UPS Setup
This chapter describes:
S Equipment inspection
S Floor loading and clearances
S Removing and replacing the cabinet doors
S Unloading the cabinet(s)
The instructions are intended for the chief operator/system supervisor, electrical
consultants, and installation electricians. Local regulations and electrical code must be
followed during the UPS installation.
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping and packing
materials for the carrier or place of purchase and file a claim for shipping damage. If
you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier
within 15 days of receipt of the equipment; 2) Send a copy of the damage claim
within 15 days to your service representative.
NOTE Check the battery recharge date on the packaging label. If the date has expired and the batteries
were never recharged, do not use the UPS. Contact your service representative.
Floor Loading
When planning the installation, consider the UPS weight for floor loading. The
strength of the installation surface must be adequate for point and distributed
loadings. The approximate weights are shown in the following table.
Standard Model Floor Loadings
Powerware 9355 Maximum Weight Point Loading
20 kVA UPS 1160 lb (526 kg) 290 lb/in
2
(20 kg/cm
2
)
30 kVA UPS 1160 lb (526 kg) 290 lb/in
2
(20 kg/cm
2
)
EBC 36 1160 lb (526 kg) 290 lb/in
2
(20 kg/cm
2
)
EBC 72 2060 lb (934 kg) 515 lb/in
2
(36 kg/cm
2
)
Options Cabinet with Transformer 535 lb (243 kg) 134 lb/in
2
(9.4 kg/cm
2
)
Options Cabinet with MBS only 205 lb (93 kg) 51 lb/in
2
(3.6 kg/cm
2
)
Clearances
The following clearances are recommended for the Powerware 9355 UPS:
From Front of Cabinet 36 (91.4 cm) working space
From Back of Cabinet 6 (15.2 cm)
From Right of Cabinet Refer to l ocal codes for right side service access [minimum 24 (61 cm)]