EATON Powerware
®
9355 UPS (20/30 kVA) Installation and Operation Manual S 164201626 Rev B www.powerware.com
67
Chapter 10 Operation
This chapter contains information on how to use the Powerware 9355, including front
panel operation, UPS startup and shutdown, and configuring the UPS for Extended
Battery Cabinets (EBCs).
Control Panel Functions
The UPS has a four-button graphical LCD with backlight. It provides useful information
about the UPS itself, load status, events, measurements, and settings (see
Figure 49).
Power On Indicator (green)
On Battery Indicator (yellow)
Bypass Indicator (yellow)
Alarm Indicator (red)
Control Buttons
for the LCD Menu Options
Figure 49. Powerware 9355 Control Panel
The following table shows the indicator status and description:
Indicator Status Description
On The UPS is operating normally.
Green
Flashing
S The UPS is starting up or is shut down and waiting for power to return.
S A new information message is active.
S Bypass is not available.
Off The UPS is turned off and will not turn on automatically.
Yellow
On The UPS is in Battery mode.
Yellow
On The UPS is in Bypass mode.
On The UPS has an active alarm.
Red
Flashing There is a new UPS alarm condition. See “Troubleshooting” on page 87 for additional information.
Changing the Language
Press and hold the first button on the left for approximately five seconds to select the
language menu. This action is possible from any LCD menu screen.