OPERATION
EATON Powerware
®
9355 UPS (20/30 kVA) Installation and Operation Manual S 164201626 Rev B www.powerware.com
69
User Settings
The following table displays the options that can be changed by the user.
NOTE Changes to the output voltage or frequency options should be made before turning on the UPS;
otherwise, the changes do not take effect.
Table 7. User Settings
Description Available Settings Default Setting
Set Date and Time Set Month
Date: mm/dd/yyyy
Time: 24:00
01/01/2003
00:00
Display Contrast Adjust contrast with up/down arrow buttons Moderate
Change Language Select Language: <English>
Elegir idioma <Español>
Choisir la langue <Francais>
English
Set Nominal Output Voltage Output:
[120V/208V] [127V/220V]
120V/208V
Relay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/2/3/4]
Setup: [Battery Low] [On Battery] [On Bypass] [UPS ok]
[custom] [empty]
Alarm1:empty
X-Slots(1or2)
#1: UPS ok
#2: On Bypass
#3: Summary Alarm
#4: On Battery
Signal Inputs [empty] [Logic]
(see “Programmable S ignal Inputs” on page 59)
<empty>
Serial Port Config Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
19200
Modem Config
Modem Setup <Not Installed>
Set Modem Call Events Event #0
Call modem: no
Set Modem Init String ATZ0
Set Modem Call Command None
Set Modem Communication Password None
Battery Setup
Number of Internal Battery Strings 6
Internal Battery Capacity [1 through 65535 watts per cell] 34W/cell
Number of External Battery Strings
(see “Configuring the UPS for EBCs” on page 74)
0
External Battery Capacity 120W/cell
Battery Low Alarm Level [1.750 through 1.950 volts per cell] 1.880 V/cell
Battery Charging [ABM cycling/constant] ABM cycling
Automatic Battery Tests [Enabled/Disabled]
Enabled automatically runs the battery test once a month.
Enabled
Full Power Battery Test [Enabled/Disabled] Enabled
Start Screen Eaton Powerware logo
Mimic screen
Eaton Powerware logo