COMMUNICATION
EATON Powerware
®
9355 UPS (20/30 kVA) Installation and Operation Manual S 164201626 Rev B www.powerware.com
49
4. Route the cable(s) through the opening between the two X-Slot communication
bays.
Communication Opening
Figure 34. Routing the Cables
5. Remove the communication wiring access plate from the UPS rear panel and
punch a hole in it using a Greenlee punch or similar device (see Figure 35).
Communication
Wiring Access Plate
Figure 35. Communication Wiring Access
6. Connect the cables to the appropriate location.
See“CommunicationOptions”onpage50or“ControlTerminals”onpage57
for detailed information.
7. Reinstall the communication wiring access plate.
8. Replace the UPS front door.
9. Continue to “Operation” on page 67 to start up the UPS.