SPECIFICATIONS
EATON Powerware
®
9355 UPS (20/30 kVA) Installation and Operation Manual S 164201626 Rev B www.powerware.com
86
Table 14. Battery Runtimes (in Minutes) at Full Load, 0.9 pF
Load
UPS Internal
Batteries
+(1) EBC 36 +(2) EBC 36 +(3) EBC 36
30 kVA/27 kW 10 31 56 75
20 kVA/18 kW 18 56 82 97
Load
UPS Internal
Batteries
+(1) EBC 72 +(2) EBC 72 +(3) EBC 72
30 kVA/27 kW 10 56 89 110
20 kVA/18 kW 18 83 114 162
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.