Technical service manual ecoGEO
29
2.11. Configuration of remote control options
EVU remote control
1. Used to enable the EVU electrical consumption control. The EVU control prevents
production of energy with the compressor or the auxiliary equipment. Circulator
pumps, valves and other components can be activated to consume energy from the
storage systems.
2. Used to select the operation logic of the EVU control.
a. NO: Closed contact to activate EVU control.
b. NC: Open contact to activate EVU control.
Winter / Summer remote control
1. Used to enable remote control of the SUMMER / WINTER program.
2. Used to select the program control operation logic.
A. NO: Closed contact to select WINTER, open contact to select SUMMER.
B. NC: Closed contact to select SUMMER, open contact to select WINTER.
DHW remote control
1. Used to enable remote control of DHW production.
2. Used to select the DHW remote control operation logic.
A. NO: Closed contact to enable DHW production.
B. NC: Open contact to enable DHW production.
Note: When DHW production is enabled, it will only start if there is a request according to
the parameters established as USER and if there is no higher priority service with a request.
Pool remote control
1. Used to enable remote control of pool production.
2. Used to select the pool remote control operation logic.
A. NO: Closed contact to enable pool production.
B. NC: Open contact to enable pool production.
Note: When pool production is enabled, it will only start if there is a request according to
the parameters established as USER and if there is no higher priority service with a request.
BMS remote control
1. Used to enable remote control via BMS or BMS / FBus2 communication ports through
ModBus protocol.
Note: To access the controller via the BMS or BMS2 ports, they must be configured as
MODBUS SLAVE EXTENDED.
BMS configuration
1. Used to assign the address of the BMS port.
2. Used to configure the communication parameters via the BMS port.
Note: This port can be used to connect several expansion cards for communication that
allow remote access to the controller through various protocols.