INSTRUCTIONS MANUAL
-45-
Then the following screen will be displayed.
Disconnect HP coupling. Start A/C system with LP coupling connected, press ENTER
The A/C system will recover the refrigerant into the service hoses, then the following screen will
be displayed:
D
isconnect LP coupling from A/C system, then press ENTER to continue:
The machine will recover the residual refrigerant into the service hoses, then the following
screen will be displayed:
EMPTY HOSES
Hoses pressure 4.0bar
STOP
DD/MM/YY XX:XX PM
EMPTY HOSES
ENTER
DD/MM/YY XX:XX PM
Disconnect LP coupling from A/C system end press ENTER
ENTER
DD/MM/YY XX:XX PM
Disconnect HP coupling Start A/C system with LP
coupling connected end press ENTER
Gas charged: 86g / 100 g
Tank Pressure 6.6 bar
A/C pressure 2.9 bar
Tank Temperature 25.5 °C
STOP
DD/MM/YY XX:XX PM
CHARGE