INSTRUCTIONS MANUAL
-87-
CALIBRATION
N.B. This menu is reserved for use by the technician performing final testing. It contains the
maximum safety threshold value; therefore, the bottle data may not be changed for any reason.
For assistance, call the Service Center.
Perform this operation whenever the values displayed on display do not correspond to real
values.
WARNING: The operations listed below must be performed with maximum attention and care.
In particular, always observe the following precautions.
Always place the weights at the center of the scale plate. Never exert pressure on the oil scale.
Always recover the gas in the high- and low-pressure hoses before beginning calibration of the
transducers.
From MAINTENANCE scroll to page 3 with the arrow
and select CALIBRATION, the
following screen will be displayed:
Type the code 0791 and press ENTER to confirm, the following screen will be displayed:
NOTE: press arrow
to visualize second and third page of the CALIBRATION MENU:
INSERT THE CODE TO ENTER
CALIBRATION MENU
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _