EasyManua.ls Logo

Elcon SA10A - Grounding; Check Main Contact Inputs. 1 A,1 B,1 C,1 D,2 A,2 B,2 C,2 D,3 A,3 B,3 C,3 D; Check Auxiliary Contact Inputs. 1 A, 1 B, 2 A, 2 B, 3 A, 3 B

Elcon SA10A
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 27 (40)
Rev 1 2018-03-21 www.elcon.se
Go to INDEX.
7.2.5 GROUNDING.
Resistance between from power inlet ground pin to Ground spade terminal < 0.5Ω
Resistance between from power inlet ground pin to 200A + spade terminal < 0.5Ω
Resistance between power inlet ground pin to D-Sub shield RS232 < 0.5Ω
7.2.6 CHECK MAIN CONTACT INPUTS.
1A,1B,1C,1D,2A,2B,2C,2D,3A,3B,3C,3D.
Connect ampere meter + to Red banana jack on contact.
Connect ampere meter - to Black banana jack on contact.
Test current for all main contacts should be 25 - 35mA.
Indication in service menu for each contact should be seen.
7.2.7 CHECK AUXILIARY CONTACT
INPUTS. 1A, 1B, 2A, 2B, 3A, 3B.
Connect ampere meter + to Blue banana jack
on contact.
Connect ampere meter - to Black banana jack
on contact.
Test current for all auxiliary contacts should
be 8 - 12mA.
Indication in service menu for each contact
should be seen.
To open this window in .
Click function Control unit from the menu Service.
Select tab Contacts.

Table of Contents