TR400 Programming
Programming the relay outputs, continued
Variables 08,
11, 37, 40, 44,
47, relay
output-delay
times
Output Delay Times are used to set the amount of time the set-point condition must
exist before the output will respond. The default value for these variables is one (1)
second.
Variables 09,
12, 38, 41, 45,
48, relay
output- on
times
Output On Times are used to set the minimum time that the output must be de-
energized after a set point condition occurs and the relay has been de-energized. This
value can be up to 600 seconds. The default value for these variables is one (1)
second.
Latching
outputs
The relay outputs can be set to latch by entering value 999.9 in the relays applicable
“on time” variable. The outputs will then latch when a fault is detected. This holds
the output inactive until a Reset, or the power is cycled to clear the output.