30
Rev G
S5−
−−
−TR400 Programming
How to select and change a variable’s numerical value
Exercise
The following 7-step procedure shows:
• How to enter Program Mode
• How to change from variable 01 (Max RPM) to variable 02 (PPR)
• How to change the value of variable 02 from 8 PPR to 16 PPR
• How to save the change, and exit Program Mode
Note: You can use the following 7-step procedure to select any variable, change its
value, and save the results.
Note: You can select a variable and change its value either when the TR400 is
monitoring or when it is idle.
Selecting and
displaying
variable data
To select variable 02 and display its data, press the key sequence shown in the three
(3) steps below, while viewing the result on the display.
Continued on next page
REV PROG
OUT
1
KEY
ERR
OUT
2
P r 0 2
REV
DIAG
VAR
ENTER
REV PROG
OUT
1
KEY
ERR
OUT
2
P r 0 1
ENTER
REV PROG
OUT
1
KEY
ERR
OUT
2
0 0 0 8
Step 1
Step 2
Step 3
Press
Data Entry Level, 8 PPR