Display Operation Manual BC2000 and JC2000 Controller ~ Doc. No. 2055882, Issue 5.1, June 2014 21
Change System Time and System Date
The controller time and date must be set manually to the current time to use such
features as event log and battery discharge scheduling. The time format is
HH:MM:SS (12-hour and 24-hour formats available) and the date format is either
MM/DD/YYYY or DD/MM/YYY.
Main Menu System Time
Date
Shunt Setup
Where available, a shunt is monitored by the LVD card that is installed in the
distribution panel. By default, each LVD reads just one shunt.
Main Menu Modules LVD (if installed) LVD Card # Contactor #
The following settings are configurable:
State—set to Open or Closed
Disconnect V—voltage at which the LVD opens
Reconnect V—voltage at which the LVD closes
Recon Delay—time delay after the reconnect voltage is reached before the
LVD contactor closes
Input Port Setup
Use these instructions to setup a controller TEMP/AUX input port as an auxiliary
alarm input. The input port does not need configuration if a temperature probe is
installed.
Main Menu Probes Probe #
The following are available states:
Disabled – input port is disabled
T Probe – the probe input operates as a temperature probe input. This
setting automatically configures itself if an Eltek temperature probe is
installed.
Aux NO – set the port to monitor a normally open form-C relay.
Aux NC – set the port to monitor a normally closed form-C relay.

Questions and Answers: