Display Operation Manual BC2000 and JC2000 Controller ~ Doc. No. 2055882, Issue 5.1, June 2014 47
Configurable parameters:
• Contactor – LVD contactor parameters
State: Closed/Open
Disconnect V (Disconnect Voltage): ##.## V
Reconnect V (Reconnect Voltage): ##.## V
Recon Delay (Reconnect Delay): HH:MM:SS
• AC Voltage – ring generator AC output voltage
• DC Voltage – DC voltage value at which the ringer RMS value is offset. It
should be equal to the float voltage.
• Frequency – ring frequency
• Select – priority of ring generator module:
None – Disables ring generator
Ringer A – Makes the ring generator the main ringer module
Ringer B – Makes the ring generator the backup ringer module
• PM Device – Setup parameters
Probe (1-8) – Input type; Disable; AUX_NO, AUX_NC
Relay polarity – Normal Energy / Normal De-energy
Relay type – On-Off / pulse
Pulse width – sec_(2_86400)