3 About Power System Configuration
18 User's Guide Smartpack2 Master Controller 350020.013, Issue 2.0, 2014 Jan
5 - Logs and Reports options
The options in this logical group collect and present the system log, battery log, report of
active alarms, etc.
The logs and reports are organized in following groups:
Active Alarm Log
Event Log
Battery Test Log
Inventory Report
Active Alarms Log
You can browse through the stored system alarm messages (or alarm log). The controller’s
alarm log may store up to 1000 chronological events. Each log entry contains event text,
event action, time and date. When the log is full, the oldest value is overwritten. The log is
stored in EEPROM.
Example of alarm log in Smartpack2 Master Controller’s submenu:
Logs/Report > Active Alarms
#
Description
Value
Limit
Alarm Group
Output
Note
BatteryTemp 1.1
42
30
----
---
SymmVolt 1.1
12,91
1,50
Alarm Group 15
----
RectifierError
1
1
Minor Alarm
-----
------
------
Event Log
The Event Log is a record of system related events automatically registered by the system
controller.
Example of Event Log in Smartpack2 Master Controller’s submenu:
Logs/Report > Event Log
#
Date and Time
Description
Event
Note
yyyy.mm.dd hh:mm:ss
RectifierError
MinorAl:On
yyyy.mm.dd hh:mm:ss
SymmVolt 1.4
MajorAl:On
yyyy.mm.dd hh:mm:ss
LVD close
Info:On
yyyy.mm.dd hh:mm:ss
Door alarm
MajorAl:Off
yyyy.mm.dd hh:mm:ss
OutdoorTemp 81.1
Info:Off
----
You can also save the Even Log to a storage media -- read about 8 - Up/Download
options (Data Storage Device)on page 20 or use CWUI (Controller Web-based User
Interface) or PowerSuite to delete, print and save the log to a file in your computer.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eltek Smartpack2 and is the answer not in the manual?

Eltek Smartpack2 Specifications

General IconGeneral
TypePower System Controller
Input Frequency45 - 65 Hz
Operating Temperature-40°C to +70°C
Communication PortsRS232, Ethernet
ProtocolsModbus, SNMP
Protection FeaturesOvervoltage, Overcurrent, Over Temperature