1 Introduction
2 User's Guide Smartpack2 Master Controller 350020.013, Issue 2.0, 2014 Jan
DC Power Supply Systems
SAFETY and ENVIRONMENTAL PRECAUTIONS
The product warranty becomes invalid if the following safety precautions are not followed during handling,
installation, commissioning and general use/operation of Eltek DC power supply system.
General Precautions
CAUTION: Even though the product incorporates protection circuitry and other safeguards, it can be damaged, perform
poorly or have a reduced lifetime if it is exposed to incorrect treatment during transport, installation or service.
Always handle the equipment using proper lifting techniques, do not roll, climb or drill hole in the cabinets or enclosures.
WARNING: Opening the equipment may cause terminal injury even if the mains AC supply is disconnected.
Hazardous voltages may be present inside, as large capacitors may still be charged.
Device
Hazard
Electric
Shock
G1
G2
Environmental Precautions
CAUTION: To avoid damage the equipment, keep objects clear of system ventilation inlets, outlets and system fans,
if any, ensuring the airflow through the units is not obstructed, and that the fans rotate freely. Use caution with rectifiers,
as they can reach extreme temperatures under load and normal operation.
WARNING: The installer/user is responsible for ensuring that the DC power system is not damaged by current
surges, over-voltages, etc. caused by external transients, lightning, electrostatic discharge, etc. To avoid damage
and obtain the expected system reliability, it is mandatory to always install SPDs in Eltek’s power supply systems.
Follow the instructions given in “Guidelines for Lightning and Surge Protection”, doc. 2024623.
WARNING: The electronics in the power supply system are designed for indoor, clean environment. When
installed in outdoor enclosures, it is important to keep the door closed during operation, and replace the filters on a
regular basis. Indoor installations in dusty or humid areas require appropriate air filtering of the room, or
filtering of the air entering the DC power system. Follow the instructions given in Generic Guidelines
Environmental Protection.”, doc. 2038879.
Ventilated
Hot Surface
Humidity & Dust
Protection
Current Surge
Protection
E2
E1
E3
CAUTION: This product is tested and verified according to international safety, environmental and EMC standards. Any
non-Eltek equipment installed into this product after delivery might influence the performance and could infringe the
original approvals. The installer is responsible for ensuring that the environmental properties of this product/ system do
not deteriorate during installation, and that it is performed in accordance with applying regulations.
Installations in USA and Canada must comply with NEC/CEC requirements.
Precautions during Installation
CAUTION: Read the user documentation carefully before installing and using the equipment, as installation and
operation is to be performed as described in it. Always tighten screws and bolts with the torque values recommended in
the documentation. For safety reasons, the commissioning and configuration of the equipment is only to be performed
by Eltek’s personnel or by authorized and qualified persons.
CAUTION: Before you start the electrical installation, you must always disconnect all external AC supply fuses, as well
as internal battery and load fuses/ breakers, if any.
WARNING: For safety reasons (high leakage current / high touch current) you must always connect the AC earth
wire (PE) to the terminals, before you connect the AC input cable(s).
The batteries, if any, represent a major energy hazard. To avoid short-circuit of battery poles, you must always
remove metallic objects uninsulated tools, rings, watches, etc. from the vicinity of the batteries.
WARNING: 60V and higher DC power systems are only to be installed in Restricted Access Locations (RAL).
Access must be limited by use of tool, i.e. lock and key.
Device
Hazard
Qualified
Personnel
EMC, NEC/CEC
Regard
Electric
Shock
Electric
Shock
I1
I2
I3
I4
I5
356800.183, 3v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eltek Smartpack2 and is the answer not in the manual?

Eltek Smartpack2 Specifications

General IconGeneral
TypePower System Controller
Input Frequency45 - 65 Hz
Operating Temperature-40°C to +70°C
Communication PortsRS232, Ethernet
ProtocolsModbus, SNMP
Protection FeaturesOvervoltage, Overcurrent, Over Temperature

Related product manuals