Service Instructions
127072E Rev. C
5
Section 1: Introduction
Introduction
4. Indicated position conrms valve position
5. All switching valves in normal operating position as per schematic/
instructions
1�11�2 Check connections:
1. Hydraulic components connected as per schematic enclosed or in service
manual supplied
2. Hydraulic supply connected to identied ports
3. Electrical connections terminals are secure
4. Wiring as per enclosed diagram or service manual supplied
1�11�3 When actuator is rst put into service, it should be cycled with regulated
pneumatic pressure. This is necessary because the seals have been stationary,
causing them to take a "set". Therefore, the actuator should be operated through
several cycles, exercising the seals, resulting in a service-ready condition.
1�11�4 The actuator speed of operation is determined by a number of factors including:
1. Power supply line length
2. Power supply line size
3. Power supply line pressure
4. Control valve and tting orice size
5. Torque requirements of the valve
6. Size of the actuator
7. Setting of speed controls
1�11�5 Due to the interaction of these variables, it is difcult to specify a "normal"
operating time. Faster operating times may be obtained by using one or more of
the following:
1. Larger supply lines
2. Larger control valve
3. Higher supply pressure*
4. Quick exhaust valves
*Not to exceed maximum operating pressure of actuator or control components
1�11�6 Slower operating times may be obtained by using ow control valves to meter the
exhaust. Excessive exhaust ow metering may cause erratic operation.
1�12 Actuator Operation
1�12�1 Controlled Operation: Controlled operation is accomplished by pressurizing and/or
depressurizing the appropriate cylinder inlet(s) of a double-acting or spring-return
unit by means of an appropriate control valve.
Do not exceed pressures indicated on actuator nameplate
1�12�2 Manual Operation: All pressure must be vented or equalized on both sides of the
pneumatic piston prior to manual operation.

Table of Contents

Other manuals for Emerson Bettis G2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Bettis G2 Series and is the answer not in the manual?

Emerson Bettis G2 Series Specifications

General IconGeneral
BrandEmerson
ModelBettis G2 Series
CategoryController
LanguageEnglish

Related product manuals