February 2018
Installation and Operation Manual
E2K-405-0218 Rev. 2
38
Section 4: Operation
Operation
4.5 Remote/Auto Control Operation
The actuator is shipped congured for four-wire controlunless otherwise specied at
order placement. There are additional remote control modes that can be selected via the
SETUP” mode.
NOTE:
See Table 4.4 for defaults.
Two-wire control
Three-wire control
IrDA port
Three-wire analog
Analog
Network
For installation details, see Section 3.5, Discrete Controlled Inputs.
To control the actuator via discrete inputs:
1. Enter “SETUP” mode. See Section 5.1, Entering Setup Mode.
2. Use the selector knob (NEXT/BACK) to select “CONTROL MODE” under “VALVE
CONTROL SETUP?
3. Use the control knob (NO) to select the desired control mode. See Section 5.5.2,
Valve Control Setup.
4. Exit “SETUP” mode and place selector knob in the REMOTE position.
Remote Maintained – Inching Mode
5. Apply the control signal and maintain. After 0.5 seconds the actuator will move in
the open or close direction.
6. Eliminate the control signal to stop the actuator.
Remote Momentary – Seal-ins Active
5. Momentarily pulse either OPEN or CLOSE control signal for 0.5 seconds minimum.
The actuator will move in the open or close direction to the end of travel.
6. Momentarily pulse the remote stop signal to stop the actuator movement.