Installation, Operation and Maintenance Manual
MDE 257 Rev. 1
February 2022
11
Resticted Menu Routines
Section 3: Restricted Menu Routines
Port 4 an0: not used
Port 4 an1: not used
Port 4 an2: not used
Port 4 an3: main voltage in bits
Port 4 an4: motor current in bits
Port 4 an5: terminal board type in bits
Port 4 an6: auxiliary contact of K1 contactor in bits
Port 4 an7: current range out in bits
Port 9 an0: auxiliary contact of K2 contactor in bits
Port 9 an1: status of Bluetooth module in bits
Port 9 an2: reserved. Not used for XTE3000
Port 9 an3: motor thermostat in bits
Port 9 an4: motor temperature in bits
Port 9 an5: not used
Port 9 an6: heater CMD in bits
Port 9 an7: backlight CMD in bits
3.16.4 Reversal Delay
This function sets the delay implemented as part of the instantaneous reversal feature (i.e. reverse
motor rotation). Standard value is 1.1 s.
3.16.5 Backlight
The standard value is AUTO. The backlight of display automatically switches off 2 minutes after the
last operation with the local operator interface. This option increases the life of the display since the
backlight is powered only when using the local operator interface.
With the option "ON," the backlight of the display is always powered. Use this option only when
absolutely necessary.

Other manuals for Emerson Bettis XTE3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Bettis XTE3000 and is the answer not in the manual?

Emerson Bettis XTE3000 Specifications

General IconGeneral
BrandEmerson
ModelBettis XTE3000
CategoryController
LanguageEnglish

Related product manuals