Installation, Operation and Maintenance Manual
MDE 257 Rev. 1
February 2022
15
Alarm "Conguration n°"
Section 4: Alarm "Conguration n°"
Section 4: Alarm "Configuration n°"
If the checksum of the EEPROM memory containing the data of XTE3000 settings is wrong,
exit the alarm "CONFIGURATION n°" (refer to the XTE3000 IOM).
Every configuration parameter is called "OBJECT or OBJ" and is characterized by an "OBJ
number." The number "n°" indicates the number of the OBJ that is out of range.
To clear the configuration alarm, it is necessary to set the correct value using the VIEW and SETUP
features as described in the XTE3000 IOM.
If the alarm message is "CONFIGURATION OBJ 9999," only one of the actuator parameters needs to
be changed. For example: enter the SETUP menu, then ACTUATOR SETUP, then TORQUE SETUP, then
and increase or decrease the closing torque by 1%. When the alarm message disappears, reenter the
SETUP menu, then ACTUATOR SETUP, then TORQUE SETUP, and then set the previous value.
If the alarm message is "CONFIGURATION OBJ 720 or 721 or 722 or 723," proceed as follows:
• Repower the actuator and observe the first message of the display. If the XTE3000 base
card is equipped with the "Ain/Aout" optional card, check the following parameters in the
"RESTRICTED" menu routines:
— Term board: should be set to "I24 V4"
— Card Ain/Aout: should be set to "PRESENT"
If the settings are wrong, enter the correct values and then proceed to cycle power on
the actuator.
In the following table is the list of the Objects (or parameters). The OBJECTS are sorted
according to the actuator menu. Every line of the table gives a complete description of the Object
by means of "OBJ n°," "normal value," "function," and "description and ranges."