3.16.18 Serial CMD
This parameter is normally set to "DISABLED." Use this option to enable OP/CL/STOP command from
Bluetooth, RS232 interface.
3.16.19 Loc/Rem
This parameter is normally set to "DISABLED." Use this option to enable local OP/CL/STOP commands
also when the local selector is in REMOTE (LOC+REM).
3.16.20 Bluetooth Code
This parameter is normally set to "S/N." Use this option to select Bluetooth code between
"S/N" = actuator serial number and "V/TAG" = valve tag.
3.16.21 EFS Duty
Reserved. Not used by XTE3000.
3.16.22 Spring Action
Reserved. Not used by XTE3000.
3.16.23 EFS EL.CMD
Reserved. Not used by XTE3000.
3.16.24 ESD Input Mode
Reserved. Not used by XTE3000.
3.16.25 CMD-filter
This parameter is normally set to 1. The maximum value is 32. Use this option to set the filter level of
OP/CL/ST commands.
Set the above parameter to 100 if a fast reaction is required in response to open and
close commands.
The setting causes the following changes:
• Control mode in local and remote changes to "push to run."
• Filtering reduced to the minimum.
3.16.26 ESD/INT-filter
This parameter is normally set to 1. The maximum value is 32. Use this option to set the filter level of
ESD/INT commands.
3.16.17 New FW
This parameter is normally set to "DISABLED." Use the option ENABLED only if the base card
firmware must be updated. Set the back to DISABLED after upgrading the firmware. Refer to
the appropriate instructions relevant to firmware upgrades.