Installation, Operation and Maintenance Manual
MDE 257 Rev. 1
February 2022
13
Resticted Menu Routines
Section 3: Restricted Menu Routines
3.16.8 Torque Sensor
This routine is used in-house to set torque sensor parameters. Do not enter into this routine; if this
occurs, press NO when the message TORQUE SENSOR CHANGE? is displayed.
3.16.9 Speed Band
The standard value is 10. The value is automatically adjusted as a function of the number of motor
poles stated in the motor data section of the NAMEPLATE menu.
3.16.10 Base Temp. Ref.
The standard value is 2 °C. When the temperature inside the electronics compartment is less than the
above value, the heater of the base card is powered.
3.16.11 LCD Temp. Ref.
The standard value is -5 °C. When the temperature inside the terminal board compartment is less
than the above value, the heater of the LCD display is powered.
3.16.12 TERM Temp. Ref.
The standard value is 0 °C. When the temperature inside the terminal board compartment is less than
the above value, the heater on the terminal board cards is switched on.
3.16.13 Torque Function
This parameter is normally set to "STANDARD."
3.16.14 Interlock Mode
This parameter is normally set to "STANDARD" and INTERLOCK function is available. If the
INTERLOCK MODE is set in "ADVANCED" the XTE3000 use the Interlock input as PST commands.
INTERLOCK OPEN becomes command to carry out PST in open direction. INTERLOCK CLOSE
becomes command to carry out PST (Partial Stroke Test) in close direction. PST function are
performed only if the actuator is fully open or closed.
3.16.15 Sleep
This parameter is normally set to "DISABLED." Use the option to enable SLEEP function.
Refer to the XTE3000 Sleep Mode manual for a detailed description of this function.
3.16.16 MR in Sleep
This parameter is normally set to "OFF." Use this option to set MR to OFF or ON when the
SLEEP function is enabled. Refer to the XTE3000 Sleep Mode manual for a detailed description of
this function.

Other manuals for Emerson Bettis XTE3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Bettis XTE3000 and is the answer not in the manual?

Emerson Bettis XTE3000 Specifications

General IconGeneral
BrandEmerson
ModelBettis XTE3000
CategoryController
LanguageEnglish

Related product manuals