Resticted Menu Routines
Section 3: Restricted Menu Routines
Reserved Routines
• SW type
• Term. board
• Additional var.
• Reversal delay
• Backlight
• 4 - 20 mA config.
• Current sensor
• Torque sensor
• Speed band
• Base temp. ref.
• LCD temp. ref.
• Term. temp. ref.
• Torque function
• Interlock mode
• Sleep mode
• MR in sleep
• New FW
• Serial CMD
• Loc/Rem
• Bluetooth code
• EFS duty
• Spring action
• EFS. EL. CMD
• ESD input mode
• CMD filter
• ESD-INT filter
3.1 Torque Stop Zone
If the torque limit is reached in the position interval "0 to torque stop zone" and "100-torque
stop zone to 100" and opening or closing stroke limits are set by torque, then the XTE3000
considers the reached position as "end of travel." If the torque limit is reached at a position between
"torque stop zone" and "100-torque stop zone," then the XTE3000 will generate an alarm. If the
torque limit is not reached the warning "wrong stroke limit" is generated. Standard value = 5%.
3.2 Speed Bypass
This is the time needed to update the motor speed after receipt of an open or close command.
Standard value = normally >1.5 s (depends on actuator type).