BACnet The RS485 Network and Hardware Setup6-15
5. Locate the device you added to the network list
(press
and to scroll through the list) and
highlight with the cursor. Press
for Com-
missioning.
Figure 6-13
- Commissioning Screen
If there is more than one route, select which route the
device is on. The route may be MS/TP or IP.
6. If this is the first commission after a reboot of the
E2 (or
a new BACnet route is created), the E2
will display a “search dialog” showing the E2 is
searching for BACnet devices on that route.
7. The E2 will present a list of
device IDs for a set
of devices found during the scan when the search
is complete. Choose which device (and subse-
quent device ID) to associate with
that E2 BAC-
net application.
8. The same list will appear for subsequent commis-
sioning to associate new devices quickly.
A rescan is needed if a new BACnet device is con-
nected on the route. Initiate the scan by pressing
-
Rescan.

Table of Contents

Other manuals for Emerson E2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson E2 and is the answer not in the manual?

Emerson E2 Specifications

General IconGeneral
ModelE2
ManufacturerEmerson
CategoryController
Power Supply24 VAC/VDC
Communication ProtocolsEthernet
Output TypeRelay, Analog
Communication ProtocolEthernet
ApplicationRefrigeration and HVAC system control

Related product manuals