Loading...
The 16AI, 8IO, and MultiFlex Inputs Input and Output Setup9-5
207-0100 Analog Liquid
Level
Down
1. Connect RED
power wire to
+12VDC source
on input board.
2. Connect BLACK
g
round wire to
odd numbered ter-
minal.
3. Connect GREEN
s
ignal wire to
even numbered
terminal.
207-1000 Refrigerant
Level Trans-
ducer (Hansen
Probe)
Down
1. Wire BLACK ground
wire from “GND”
sensor terminal to odd
numbered board ter-
minal.
2. Wire GREEN signal
wire
from “SIGNAL”
sensor terminal to
even numbered board
terminal.
3. Wire RED power wire
from “P
OWER” sen-
sor terminal to
+
12VDC terminal on
board.
203-1902 Dewpoint Probe
Up
1. Connect the WHITE
and GREEN wires to
AC1 and AC2 power
terminals.
2. Connect BLACK
g
round wire to odd
numbered board termi-
nal.
3. Connect RED signal
wire
to even numbered
board terminal.
P/N Sensor
Input Type
Dip Switch
Wiring
Table 9-1