4195KA, KB, KC, and KS Controllers
Instruction Manual
Form 5207
April 2007
1-5
Table 1-1. Specifications
Available Configurations
See table 1-2
Input Signal (Process Sensor Range
(1)
)
Lower and Upper Range Limits: See tables 1-3
and 1-4
Maximum Allowable Operating Limits: See
tables 1-3 and 1-4
Output Signal
(1)
Proportional-Only, Proportional-Plus-Reset,
or Proportional-Plus-Reset-Plus-Rate Range:
0.2 to 1.0 bar or 0.4 to 2.0 bar (3 to 15 psig or 6
to 30 psig)
Differential Gap Range: 0 and 1.4 bar (0 and 20
psig) or 0 and 2.4 bar (0 and 35 psig)
Action: Field-reversible between direct
(increasing sensed process pressure increases
output pressure) or reverse (increasing sensed
process pressure decreases output pressure).
Process Scale
Standard scale is matched to the range of the
sensing element, with the exception of receiver
controllers. Optional
(2)
scales are available.
Process Connections
Standard: 1/4 NPT, internal, stainless steel (all
input ranges)
Optional: 1/2 NPT, see table 1-5
Supply and Output Connections
1/4 NPT, internal
Supply Pressure Requirements
(3)
See table 1-6
Supply Pressure Medium
Air or natural gas
(4)
Remote Set Point Pressure Ranges
0.2 to 1.0 bar or 0.4 to 2.0 bar (3 to 15 psig or 6
to 30 psig)
Controller Adjustments
Proportional Band
(1)
: 5 to 500% of process
input span
Reset
(1)
: Adjustable from 0.01 to more than 74
minutes per repeat (from 100 to less than 0.0135
repeats per minute)
Rate
(1)
: Adjustable from 0 to 20 minutes
Differential Gap
(1)
Controllers: Adjustable from
5 to 100% of process scale range
Set Point: Adjustable from 0 to 100% of the scale
span
Controller Performance
Repeatability
(1)
: 0.4% of output span
Dead Band
(1)
: Less than 0.4% of process scale
span
Typical Frequency Response: 1.5 hertz and 90
degree phase shift with 3.05 m (10 feet) of 6.4
mm (1/4-inch) tubing and 1639 cm
3
(
100 cubic
inch) volume
Steady-State Air Consumption
(1,5,6)
0.2 to 1.0 Bar (3 to 15 Psig) Output: 0.1 normal
m
3
/hr (3.5 scfh)
0.4 to 2.0 Bar (6 to 30 Psig) Output: 0.14 normal
m
3
/hr (5.0 scfh)
Delivery Capacity
(5)
0.2 to 1.0 Bar (3 to 15 Psig) Output: 5.9 normal
m
3
/hr (240 scfh)
0.4 to 2.0 Bar (6 to 30 Psig) Output: 10.4 normal
m
3
/hr (350 scfh)
Operative Ambient Temperature Limits
(1,3,7)
−40 to 71_C (−40 to 160_F)
Exhaust Capacity
(5)
0.2 to 1.0 Bar (3 to 15 Psig) Output: 4.6 normal
m
3
/hr (186 scfh)
0.4 to 2.0 Bar (6 to 30 Psig) Output: 7.0 normal
m
3
/hr (295 scfh)
Hazardous Area Classification
Complies with the requirements of ATEX Group II
Category 2 Gas and Dust
continued