6.2.5 Open Limit Conguration
• Move switch SW3 to position ON
• Drive the actuator to the open position using the handwheel
• Move switch SW4 to position 1
• Move switch SW6 to position 0
• Conrm by pushing ENTER pushbutton SW5
• When pushing SW5, the red LED switches on for conrmation
• Exit set up conguration, moving switch SW3 to position 1 or proceed with the
next parameter
6.2.6 Close Limit Conguration by Torque
• Move switch SW4 to position 2
• Move switch SW6 to position 0
• Move switch SW3 to position ON
• Conrm by pushing ENTER pushbutton SW5 (red LED switch on)
• Operate the actuator to closing direction by local/remote control and wait until it
stops by torque
• When the setting is completed, the red LED switches off
• Exit set up conguration, moving switch SW3 to position 1 or proceed with the
next parameter
6.2.7 Open Limit Conguration by Torque
• Move switch SW4 to position 3
• Move switch SW6 to position 0
• Move switch SW3 to position ON
• Conrm by pushing ENTER pushbutton SW5 (red LED switch on)
• Operate the actuator to opening direction by local/remote control and wait until
it stops by torque
• When the setting is completed, the red LED switches off
• Exit set up conguration, moving switch SW3 to position 1 or proceed with the
next parameter