Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
October 2020
33
Actuator Conguration
Section 6: Actuator Conguration
NOTE
During the new stroke limit setup, the minimum range between open and close limit
position has to be at least 45 degree of the valve position; if the above condition is not
respected, the setup will not be successful and stroke limit error alarm will be signalized
(red LED blinking). The red LED will continuously ash when the actuator is in setup
functionality (dip switch SW3 in ‘on’ position) and rotary switches SW4 and SW6 are in
one of the following positions:
a. SW4=3 and SW6=0
(stroke limit of open conguration by torque)
b. SW4=2 and SW6=0
(stroke limit of close conguration by torque)
c. SW4=1 and SW6=0
(stroke limit of open conguration by position)
d. SW4=0 e SW6=0
(stroke limit of close conguration by position)
The alarm is then reset by:
a. Switching off and on the actuator
b. Doing a new correct stroke limit setup in one of the 4 possible combinations.
!
WARNING
In conguration phase, touch only the conguration area of the logic board; don’t touch
the actuator in its other parts.
6.2.8 Stroking Time Selection in Closing
• Enter set up conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 4
• Move switch SW6 to positions 4, 6, 8 for the requested stroking time according
to the table below
• Push ENTER pushbutton SW5 to conrm
• When pushing SW5, the red LED switches on for conrmation
• The selected stroking time in closing is now set
• Exit set up conguration (move switch SW3 to position 1) or proceed with
the next parameter