Actuator Conguration
Section 6: Actuator Conguration
6.4 Hardware Conguration for Monitor Relay
The Monitor Relay indicates the followings failures:
• Loss of power
• Stop by Torque out of limits
• Direction failure
• Temperature too high
• Position sensor failure
• Local control panel with selector in local position
• Valve jammed
• Hardware malfunction
• Alarm on the local control panel (if present)
• Stroke failure
• Missing input 4-20 mA (if OM1 optional module present)
• A Manager local control (if Bluetooth is present)
The Monitor relay contacts can be set as CLOSE or OPEN by changing the welding of
JUMPER J31 on logic board. As a default setting, pins 2 and 3 are welded together, and the
Monitor relay contact operates as follows:
— contact CLOSE in normal condition with relay energized, and OPEN in
case of malfunction (relay is de-energized).
In case of request, if contact must be OPEN in normal condition and CLOSE in case of
malfunction, the contact of JUMPER J31 must be modied welding pins 1 and 2 together.
!
WARNING
Conguration of Monitor Relay by means JUMPER J31 is a hardware conguration. For this
reason, to congure Monitor Relay is mandatory manage actuator without power supply.