Actuator Conguration
Section 6: Actuator Conguration
6.2.11 Conguration of the Torque Limiting Device in Opening
Opening torque limits: 50%, 75% and 100% of the nominal torque. The nominal torque
corresponding to 100% is set in-house and stated in the name plate.
• Enter set up conguration: move switch SW3 to position ON (conguration function)
• Move SW4 switch to position 7
• Move switch SW6 to positions 2, 5 or 9 for the requested Torque value
(in percentage) in opening
• Push ENTER pushbutton SW5 to conrm
• When pushing SW5, the red led switches on for conrmation
• The setting of the torque limiting device in opening is now complete
• Exit set up conguration (move switch SW3 to position 1) or proceed
with the next parameter
!
WARNING
To
rque switches setting must be done only with the authorization of the valve manufacturer
,
considering the specic valve gures.
6.2.12 Reverse Mode Conguration
• Enter set up conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 8
• Move switch SW6 to position:
1 counter-clockwise (CCW) ON
0 counter-clockwise
(CCW) OFF
• Push ENTER pushbutton SW5 to conrm
• When pushing SW5, the red LED switches on for conrmation
• Reverse mode (CCW) set is now completed
• Exit set up conguration (move switch SW3 to position 1) or proceed with
the next parameter