L1 L2 L3 35 36 32 33 34 20 21
CLC1 CLC2 OPC1 OPC2
22 23 24 25 26 27 28 29 30 311 2 3 4
October 2020
Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
22
Installation
Section 4: Installation
4.11 Base Wiring Diagram
Figure 11
!
WARNING
It is under user responsibility to limit the rated impulse voltage level at 1500 V.
3. Contacts shown in intermediate position CLC1-CLC2 end of travel signaling in closing.
Contacts shown in intermediate position OPC1-OPC2 end of travel signaling in opening.
4. Output contact rating 240 V AC / 5 A ; 30 V DC / 5A ; 120 V DC / 0.5 A.
Output contacts (when used) have to be feed with the same external voltage.
5. Control command rating 24 to 120 V AC or DC.
Control signal: minimum duration>600 ms
6. Blinker or Local Selector monitoring function (when OM3 is present) to be congured
Internal supply 24 V DC
Internal supply 24 V DC
Contact open for actuator closing
Contact close for actuator opening
Contact open for actuator closing
Contact close for actuator opening
External supply 24 / 120 V AC or 24 / 120 V DC
External supply 24 / 120 V AC or 24 / 120 V DC
a. Standard conguration
b. 2 wires setting (to be congured)
Figure 12
NOTE
1. Power connection L1-L2 for V DC or V AC single phase motor supply from 24 V to
48 V or from 100 V to 240 V.
Power connection L1-L2-L3 for 3-phase motor supply from 208 V to 575 V
(check the actuator label for the correct voltage to be applied).
2. Remote command options.
Note 1 Note 4, 6Remote commands
(Note 2, 5)
MONITOR
RELAY
GROUND
BLINKER LOCAL
SELECTOR
RELAY
Output contacts
(Note 3, 4)
Optional
module OM3