Actuator Conguration
Section 6: Actuator Conguration
6.2.2 Close Limit Conguration by Position
Enter set up conguration:
Move switch SW4 to position 2
Move switch SW6 to position 1
Move switch SW3 to position ON
Conrm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for conrmation
Exit set up conguration, moving switch SW3 to position 1 or proceed with the
next parameter
6.2.3 Close Limit Conguration
Move switch SW3 to position ON
Drive the actuator to the close position using the handwheel
Move switch SW4 to position 0
Move switch SW6 to position 0
Conrm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for conrmation
Exit set up conguration, moving switch SW3 to position 1 or proceed with the
next parameter
6.2.4 Open Limit Conguration by Position
Move switch SW4 to position 3
Move switch SW6 to position 1
Move switch SW3 to position ON
Conrm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for conrmation
Exit set up conguration, moving switch SW3 to position 1 or proceed with the
next parameter