October 2020
Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
36
Actuator Conguration
Section 6: Actuator Conguration
6.2.13 Actuator Model Selection
The frames relevant to models 63/125 and 250/500 can be set to operate with a 63 Nm
or 125 Nm motor and a 250 Nm or 500 Nm motor respectively. The difference is based on
the technical characteristics of the electric motor itself.
Actuator model 63
• Enter set up conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 9
• Move switch SW6 to position 0
• Conrm by pushing ENTER pushbutton, SW5
• When pushing SW5, the red LED switches on for conrmation
• Exit set up conguration (move switch SW3 to position 1) or proceed with
the next parameter
Actuator model 125
• Enter set up conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 9
• Move switch SW6 to position 1
• Conrm by pushing ENTER pushbutton SW5
• When pushing SW5, the red LED switches on for conrmation
• Exit set up conguration (move switch SW3 to position 1) or proceed with
the next parameter
Actuator model 250
• Enter set up conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 9
• Move switch SW6 to position 0
• Conrm by pushing ENTER pushbutton SW5
• When pushing SW5, the red LED switches on for conrmation
• Exit set up conguration (move switch SW3 to position 1) or proceed with
the next parameter