Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
October 2020
37
Actuator Conguration
Section 6: Actuator Conguration
Actuator model 500, 1000, 2000
Enter set up conguration: move switch SW3 to position ON (conguration function)
Move switch SW4 to position 9
Move switch SW6 to position 1
Conrm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for conrmation
Exit set up conguration (move switch SW3 to position 1) or proceed with
the next parameter
6.2.14 Blinker / Local Selector Conguration
Default conguration for Blinker / Local Selector relay is off (always Open). In Blinker
conguration, during actuator movement the relay changes their status each 500 ms (Motor
Running function). In Local Selector conguration (with Local Interface OM3 installed), the relay
is CLOSE when OM3 switch is on REMOTE, while it is OPEN when OM3 switch is on LOCAL.
To congure Blinker or Local Selector monitoring function (when OM3 is present):
Enter set up conguration: move switch SW3 to position ON (conguration function)
Move switch SW4 to position 4
Move switch SW6 to position 1 (Blinker) or 2 (Local Selector)
Conrm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for conrmation
Exit set up conguration (move switchSW3 to position 1) or proceed with
the next parameter