UPS System: HIPULSE E
Communication System Manual
Description of Protocol (Modbus/Jbus Interface)
Page 5-6
(04/07)
5.5 UPS\MSS TIME
The ‘UPS time request’ command is used to read the current time on the UPS.
(*) The same commands apply to UPS system configuration with MSS.
Address Meaning Size (bytes) Range / Resolution Format
40020 UPS HOURS (*) 2 0 : 23 ASCII
40021 UPS MINUTES (*) 2 0 : 59 ASCII
40022 UPS SECONDS (*) 2 0 : 59 ASCII
5.6 UPS\MSS DATE
The ‘UPS date request’ command is used to read the current date on the UPS.
(*) The same commands apply to UPS system configuration with MSS.
Address Meaning Size (bytes) Range / Resolution Format
40025 UPS DAY (*) 2 1 : 31 ASCII
40026 UPS MONTH (*) 2 1 : 12 ASCII
40027 UPS YEAR (*) 2 00 : 99 ASCII