Communication System Manual
 
  UPS System: HIPULSE E  
(Modbus/Jbus Interface)    Description of Protocol 
 
 
(04/07)
  Page 5-1  
     
5.  TECHNICAL DESCRIPTION OF THE PROTOCOL 
This section provides a detailed description of how the standard MODBUS RTU protocol is implemented in the UPS 
P/N 4550005F Operator Logic board (or MSS Operator Logic P/N 4550008I).  
For  further  information  not  supplied  herein,  please  refer  to  the  document  outlining  the  standard  MODBUS  RTU 
protocol issued by MODICON and available from its Internet site at http://www.modicon.com/techpubs 
5.1  General features of the MODBUS/JBUS RTU protocol 
The  Modbus/Jbus  RTU  protocol  is  handled  using  the  serial  line  managed  directly  by  the  Siemens  80C166M 
microcontroller, which uses the RS485 interface. 
This serial line may be used to set up a network of connected UPSs by connecting Operator Logic boards to one another 
(see Fig. 3-6). 
This function and all other settings already made to set up a network will of course be lost when the MODBUS/JBUS 
RTU protocol is selected. 
 
This  protocol  may  be  used  to  connect  the  Operator  Logic  board  to  either  a  MODBUS  MASTER  or  a  JBUS  RTU 
MASTER. This is because the JBUS RTU protocol is a subset of the MODBUS RTU protocol, and functions common 
to both protocols have been used to implement the desired requests.