UPS System: HIPULSE E
Communication System Manual
Description of Protocol (Modbus/Jbus Interface)
Page 5-24
(04/07)
Address Meaning Size Fc3 Fc4 Fc6 Fc16
Can.
Prg.
UPS MSS
40200 Alarm History command 2 X X X X X
40201 Inverter command 2 X X X X X
40202 Rectifier command 2 X X X X
40203 Mains command 2 X X X X X
40204 Battery test command 2 X X X X
40205 Battery charge command 2 X X X X
40206 Alarm reset command 2 X X X X X
Legend :
Address: Parameter/data address
Meaning: Specifies meaning of parameter/data
Size: Size of parameter/data in bytes
Fc3 Function code nr. 3 - read holding register
Fc4 Function code nr. 3 - read input register
Fc6 Function code nr. 6 - write single register
Fc16 Function code nr. 16 - write multiple register
Can. Can Bus not available
UPS Parameters/Measurements/Alarms valid for the UPS
MSS Parameters/Measurements/Alarms valid for the MSS