Operation
45 Liebert
®
iCOM
®
for Liebert DSE
Figure 32 Return Compensation in Unit View
Figure 33 Return Compensation control band
Return
Compensation
in Unit View
-100%
S115 Return
Compensation Band
S114 Return
Compensation Setpoint
S115 Return Compensation Value
Temperature Setpoint
(Sensor set to either Supply Sensor
or Remote Sensor )
New air temperature
setpoint modified by
compensation