Operation
59 Liebert
®
iCOM
®
for Liebert DSE
FC LOCKOUT 2 Sec 2 sec / 0 – 9999 * WRN
COMPRESSOR(S) LOCKOUT 2 Sec 2 sec / 0 – 9999 * WRN
COMP 1 SHORT CYCLE 0 Sec 0 - 9999 MSG
COMP 2 SHORT CYCLE 0 Sec 0 - 9999 MSG
No Power 0 0 seconds / 0-9999 WRN
Condensate 1 Failure 0 5 seconds / 0-9999 WRN
Condensate 2 Failure 0 5 seconds / 0-9999 WRN
EC Fan Fault 0 10 seconds / 0-9999 ALM
HIGH SUP TEMP 0 30 seconds / 0-9999 WRN
LOW SUP TEMP 0 30 seconds / 0-9999 ALM
REDUCED ECO AIRFLOW 0 3 seconds / 0-9999 WRN
ECO HI TEMP OVERRIDE 0 10 seconds / 0-9999 WRN
TEMP CTRL SENSOR FAIL 0 3 seconds / 0-9999 ALM
HIGH DEW POINT 0 30 seconds / 0-9999 WRN
LOW DEW POINT 0 30 seconds / 0-9999 WRN
HI DEW POINT SENSOR A 0 30 seconds / 0-9999 WRN
LOW DEW POINT SENSOR A 0 30 seconds / 0-9999 WRN
HIGH REMOTE SENSOR 0 30 seconds / 0-9999 WRN
POWER “A” FAILURE 0 10 seconds / 0-9999 ALM
POWER “B” FAILURE 0 10 seconds / 0-9999 ALM
AIRFLOW SENSOR FAILURE 0 10 seconds / 0-9999 WRN
HUM CTRL SENSOR FAIL 0 30 seconds / 0-9999 WRN
LOSS OF FLOW 0 5 seconds / 0-9999 ALM
STAT PRES SENSOR FAIL 0 120 seconds / 0-9999 ALM
LOW STATIC PRESSURE 0 120 seconds / 0-9999 WRN
HIGH STATIC PRESSURE 0 120 seconds / 0-9999 WRN
STATPRES OUT OF RANGE 0 150 seconds / 0-9999 WRN
DAMPER FAILURE 0 10 seconds / 0-9999 ALM
BMS DISCONNECTED 0 ENABLED / DIS - ENAB WRN
Table 12 Possible event settings—events listed may vary by specific unit and options order
Event
Internal Delay
(Before Action Occurs)
Default Delay / Selectable
(Before Action Occurs)
Type
(default)