EasyManua.ls Logo

Emerson Liebert iCOM - Ite Scan; Ommunication -Building Management Systems, Liebert

Emerson Liebert iCOM
172 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
External Communication—Building Management Systems, Liebert SiteScan
®
89 Liebert
®
iCOM
®
for Liebert DSE
™
6.0 EXTERNAL COMMUNICATION—BUILDING MANAGEMENT SYSTEMS, LIEBERT
SITESCAN
®
Liebert iCOM is capable of communicating with external monitoring systems, such as Building
Management Systems (BMS), Network Monitoring Systems (NMS), Liebert's SiteScan
®
Web and
others.
Each Liebert iCOM-controlled cooling unit is equipped with Liebert IntelliSlot
®
plug-in slots for use
with optional communication cards. Two hot-swappable cards are available to provide remote
communication to the Liebert iCOM.
The Liebert IntelliSlot
®
Unity
™
Card monitors and manages a range of operating parameters, alarms
and notifications. Liebert IntelliSlot Unity cards deliver:
• Emerson Protocol for Trellis
™
, Liebert SiteScan
™
and Liebert Nform
®
• Embedded LIFE
™
Technology for Remote Service Delivery
• SNMP (v1/v2c/v3) for Network Management Systems
• HTTP/HTTPS for Web page viewing
• SMTP for e-mail
• SMS for mobile messaging
• Modbus RTU-Modbus Remote Terminal Unit (RTU) communication protocol for Building
Management Systems over a RS-485 serial network (also called Modbus RTU RS-485)
• Modbus TCP-Modbus Transmission Control Protocol for Building Management Systems over an
Internet or LAN
• BACnet IP—BACnet over Internet Protocol for Building Management Systems over the Internet
or a LAN
• BACnet MSTP—BACnet Master-Slave/Token-Passing (MSTP) communication protocol for
Building Management Systems over an RS-485 serial network (also called BACnet MSTP RS-485)
The Liebert IntelliSlot Unity platform supports communication with up to two third-party protocols
simultaneously. Velocity V4 monitoring protocol is required to ensure monitoring connectivity with
the Liebert IntelliSlot IS-UNITY-DP. Velocity V4 protocol is standard in Liebert iCOM software
version PA1.04.033 and later.
Another communication option is the Liebert IntelliSlot SiteLink-E
®
Card (IS-485EXI), which
provides ground fault isolated connection to a Liebert SiteLink-E for monitoring and management.
The Liebert IS-485EXI is compatible with all Liebert iCOM software versions. See the Liebert Web
site for the latest supported protocols, monitoring reference information and SNMP MIBs:
www.liebert.com

Table of Contents