Status alarms and Status Alarm Severity (continued)Table 5-2:
Alarm code Status message Default severity Notes Configurable?
A035 Meter Verification Aborted
Informational
Applies only to transmitters with
Smart Meter Verification.
Yes
A100 mA Output 1 Saturated
Informational
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A101 mA Output 1 Fixed
Informational
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A102 Drive Overrange
Informational
Yes
A103 Data Loss Possible (Totals
and Inventories)
Informational
Applies only to flowmeters with the
standard core processor.
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A104 Calibration in Progress
Informational
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A105 Slug Flow
Informational
Yes
A106 Burst Mode Enabled
Informational
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A107 Power Reset Occurred
Informational
Normal transmitter behavior; oc-
curs after every power cycle.
Yes
A108 Basic Event 1 On
Informational
Applies only to basic events. Yes
A109 Basic Event 2 On
Informational
Applies only to basic events. Yes
A110 Frequency Output Satura-
ted
Informational
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A111 Frequency Output Fixed
Informational
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A112 Upgrade Transmitter Soft-
ware
Informational
Applies only to systems with trans-
mitter software earlier than v5.0.
Yes
A113 mA Output 2 Saturated
Informational
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A114 mA Output 2 Fixed
Informational
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A115 No External Input or Polled
Data
Informational
Yes
A118 Discrete Output 1 Fixed
Informational
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A119 Discrete Output 2 Fixed
Informational
Can be set to either Informational or
Ignore, but cannot be set to Fault.
Yes
A131 Meter Verification in Pro-
gress: Outputs to Last
Measured Value
Informational
Applies only to transmitters with
Smart Meter Verification.
Yes
Configure device options and preferences
Configuration and Use Manual 75