14
Reference Manual
00809-0300-4410, Rev BA
Configuration
January 2018
Configuration
Manually rerange the transmitter by entering range points
Field Communicator
AMS Device Manager
1. Right click the device and select Configure.
2. Select Manual Setup and select Analog Output.
3. Enter upper and lower range values in the Range Limits box and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
LOI
Reference Figure 2-8 to rerange the transmitter using the LOI. Enter values using SCROLL and ENTER
buttons.
Figure 2-8. Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without entering
specific 4 and 20 mA points.
Field Communicator
AMS Device Manager
1. Right click the device, select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure button and follow the screen prompts range the transmitter.
LOI
Use Figure 2-9 to manually rerange the device using an applied pressure source with an LOI.
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
2, 2, 2, 1
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
2, 2, 2, 2
RERANGE
ENTER VALUES
ENTER VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
ENTER VALUES
LRV
URV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU