Table 5-4: Holding Register Sakura_TempErrorConfig (1212)
Value Definition Description
0 Default The tank hub will reply with default temperature value
999.9 °C. It is recommended to keep the configuration as
Default.
1 Last Valid The tank hub will reply with the last good temperature
value.
2 Invalid Value The tank hub will reply with the temperature value that
is present in the tank hub even if the temperature is
considered to be invalid.
(1)
3 User Defined The tank hub will reply with the temperature value
configured in holding register 1206 (see Table 5-5).
(1) Note that the tank hub will use -300.0 °C to indicate invalid temperature (configurable
in holding register 6096).
Figure 5-3 shows an examplewhere holding register Sakura_TempErrorConfig (1212) is set
to value 1. The tank hub will reply with the latest good temperature value.
Figure 5-3: Example: Holding Register Sakura_TempErrorConfig (1212) Set to Value 1
Table 5-5: User Defined Invalid Temperature Value
Input register Register
number
Default
value
Description
Emul_Temp_ErrVal_1_10_C 1206 0 User defined invalid temperature value in
1/10 °C.
Optional configuration and settings Manual Supplement
August2023 00809-0800-2410
24 Emerson.com/Rosemount