140
Reference Manual
00809-0100-4021, Rev JA
Configuration
April 2017
Configuration
FAILED_ENABLED
This parameter contains a list of failures that makes the device non-operational and causes an alert to be
sent. Below is a list of the failures with the highest priority first.
1. Electronics
2. NV Memory
3. HW/SW Incompatible
4. Primary Value
5. Secondary Value
FAILED_MASK
This parameter masks any of the failed conditions listed in FAILED_ENABLED. A bit on means the
condition is masked from alarming and will not be reported.
FAILED_PRI
Designates the alerting priority of the FAILED_ALM, see Alarm priority” on page 154. The default is 0,
and the recommended values are between 8 and 15.
FAILED_ACTIVE
This parameter displays the active alarms. Only the highest priority alarm will be displayed. This priority
is not the same as the FAILED_PRI parameter described above, but is hard coded within the device and is
not user configurable.
FAILED_ALM
Alarm indicating a failure within a device which makes the device non-operational.
MAINT_ALARMS
A maintenance alarm indicates the device, or some part of the device, needs maintenance soon. If the
condition is ignored, the device will eventually fail. There are five parameters associated with
MAINT_ALARMS.
MAINT_ENABLED
The MAINT_ENABLED parameter contains a list of conditions indicating the device, or some part of the
device, needs maintenance soon.
Below is a list of the conditions, with the highest priority first.
1. Primary value degraded
2. Secondary value degraded
3. Configuration error
4. Calibration error
MAINT_MASK
The MAINT_MASK parameter masks any of the failed conditions listed in MAINT_ENABLED. A bit on
means that the condition is masked out from alarming and will not be reported.
MAINT_PRI
MAINT_PRI designates the alarming priority of the MAINT_ALM, see “Process alarms” on page 154. The
default is 0 and the recommended values is 3 to 7.